Voice Evacuation System

Voice Evacuation System

  • Post by : admin
  • Jan, 06 2020
  • Blog
  • Comments Off on Voice Evacuation System

Features:

● AB line speaker output of two zones, independent switch with master volume, treble and bass adjustment
● Support speaker line detection (light load, overload, open circuit and short circuit)
● One channel audio input, two-zone paging microphone, support offline detection
● Built-in primary and standby 240W digital amplifier module, auto switch to standby amplifier when the primary one breaks down
● Support AC/DC power supply, and AC/DC automatic

Items Index
Rated power output 240W (Note: please connect high impedance speaker within this load)
Rated voltage output 100V
Power supply AC220V/50Hz
Sensitivity Microphone 5mv(±1mv)
Line input 1VRMS(±100mv)
SNR Microphone ≥70dB
Line input ≥80dB
Frequency response Microphone 100Hz~10KHz(±3dB)
Line input 80Hz~15KHz(±3dB)
The ratio of source electromotive force ≥12dB
Total harmonic distortion ≤0.5%
Tone adjustment range ±11±2 dB
Rated power consumption 350W
AC-DC power supply switching time No intermittent
Main and standby amplifier switching time No intermittent
Battery life of 12AH (two batteries in series form 24V) 2H (voice evacuation works normally)
Machine dimensions 500×400×180mm
Net weight 15KG (without batteries)
Battery Size ≤150*100*100mm (2 pcs)
Voltage 12V; (two batteries in series form 24V)